Official summary
What is being procured?
Delivery of three (3) 500 MVA, 220/132 kV autotransformers for substations for out-door installation. Rated power: 500 MVA Rated voltage Ur: 220/132 kV Max. operating voltage Umax: 245 kV Frequency: 50 Hz Cooling: ONAN/ONAF Corrosion Protection: C5VH or above Maximum sound power level: 92 dB(A), preferably lower, (at rated voltage 220/132 kV) Short circuit level 40kA
Notice history
Procurement timeline
Follow the main stages and updates linked to this procurement procedure.
No other related notice has been identified yet.
Data is restructured for easier reading. The official notice and procurement documents always prevail.
Source and reliability
TED · 552549-2026. Checked on Aug 24, 2026, 3:05 PM.
Data is restructured for easier reading. The official notice and procurement documents always prevail.