Officielt resumé · English
Hvad indkøbes?
Delivery of three (3) 500 MVA, 220/132 kV autotransformers for substations for out-door installation. Rated power: 500 MVA Rated voltage Ur: 220/132 kV Max. operating voltage Umax: 245 kV Frequency: 50 Hz Cooling: ONAN/ONAF Corrosion Protection: C5VH or above Maximum sound power level: 92 dB(A), preferably lower, (at rated voltage 220/132 kV) Short circuit level 40kA
Vejledende maskinoversættelse. Det officielle resumé er fortsat gældende.
Officielt resumé · English
Delivery of three (3) 500 MVA, 220/132 kV autotransformers for substations for out-door installation. Rated power: 500 MVA Rated voltage Ur: 220/132 kV Max. operating voltage Umax: 245 kV Frequency: 50 Hz Cooling: ONAN/ONAF Corrosion Protection: C5VH or above Maximum sound power level: 92 dB(A), preferably lower, (at rated voltage 220/132 kV) Short circuit level 40kA
Meddelelseshistorik
Udbudsforløb
Følg de vigtigste faser og opdateringer i dette udbud.
Der er endnu ikke fundet en anden relateret meddelelse.
Data er omstruktureret for at være lettere at læse. Den officielle meddelelse og udbudsdokumenterne er altid gældende.
Kilde og pålidelighed
TED · 552549-2026. Kontrolleret 24. aug. 2026 15.05.