What is being procured?
Delivery of four (4) variable Shunt Reactor for outdoor installation at substation Idom-lund: Rated voltage Ur: 235 kV Power rating: 60-120 Mvar Regulation Range: 50 % or above Type of regulation: onload (OLTC) Cooling: ONAN Maximum sound power level: 80 dB(A), preferably lower, (at max. operating voltage 245 kV) Corrosion Protection: C5VH or above Max. operating voltage Umax: 245 kV Frequency: 50 Hz Short circuit level 40kA Magnetic characteristic: The core must be linear up to 1.5 times rated voltage.